Unlike other cables, fire resistant cables should work even when immediately uncovered to the fireplace to keep important Life Safety and Fire Fighting tools working: Fire alarms, Emergency Lighting, Emergency Communication, Fire Sprinkler pumps, Fireman’s Lift sub-main, Smoke extraction fans, Smoke dampers, Stair pressurization fans, Emergency Generator circuits and so forth.
In order to categorise electric cables as fireplace resistant they’re required to endure testing and certification. Perhaps the primary common hearth exams on cables had been IEC 331: 1970 and later BS6387:1983 which adopted a gasoline ribbon burner check to provide a flame in which cables were positioned.
Since the revision of BS6387 in 1994 there have been 11 enhancements, revisions or new take a look at standards launched by British Standards for use and application of Fire Resistant cables but none of these appear to handle the core concern that fireside resistant cables where examined to frequent British and IEC flame check standards usually are not required to perform to the identical fireplace efficiency time-temperature profiles as every different structure, system or part in a building. Specifically, where fire resistant structures, systems, partitions, fireplace doors, hearth penetrations fire obstacles, flooring, walls etc. are required to be hearth rated by constructing regulations, they are examined to the Standard Time Temperature protocol of BS476 components 20 to 23 (also often identified as ISO834-1, ASNZS1530pt4, EN1363-1 and in America and Canada ASTM E119-75).
These checks are performed in massive furnaces to replicate real post flashover hearth environments. Interestingly, Fire Resistant cable check standards like BS 6387CWZ, SS299, IEC 60331 BS8343-1 and 2, BS8491 solely require cables to be uncovered to a flame in air and to lower final check temperatures (than required by BS476 pts 20 to 23). Given Fire Resistant cables are likely to be exposed in the same fireplace, and are wanted to make sure all Life Safety and Fire Fighting systems stay operational, this fact is perhaps surprising.
Contrastingly in Germany, Belgium, Australia, New Zealand, USA and Canada Fire Resistant cable methods are required to be tested to the identical fire Time Temperature protocol as all other constructing parts and this is the Standard Time Temperature protocol to BS476pts 20-23, IS0 834-1, EN1363-1 or ASTM E119-75 in USA.
The committees creating the standard drew on the steerage given from the International Fire Prevention Congress held in London in July 1903 and the measurements of furnace temperatures made in many hearth tests carried out within the UK, Germany and the United States. The checks had been described in a collection of “Red Books” issued by the British Fire Prevention Committee after 1903 as nicely as those from the German Royal Technical Research Laboratory. The finalization of the ASTM standard was closely influenced by Professor I.H. Woolson, a Consulting Engineer of the USA National Board of Fire Underwriters and Chairman of the NFPA committee in Fire Resistive Construction who had carried out many checks at Columbia University and Underwriters Laboratories in Chicago. The small time temperature differences between the International ISO 834-1 check as we know it at present and the America ASTM E119 / NFPA 251 exams likely stemmed from this time.
Image courtesy of MICC Ltd.
The curve as we see it today (see graph above) has turn out to be the usual scale for measurement of fire test severity and has proved relevant for most above floor cellulosic buildings. When elements, constructions, components or systems are tested, the furnace temperatures are managed to evolve to the curve with a set allowable variance and consideration for initial ambient temperatures. The standards require parts to be examined in full scale and beneath conditions of help and loading as outlined so as to characterize as precisely as attainable its features in service.
This Standard Time Temperature testing protocol (see graph right) is adopted by nearly all international locations around the world for hearth testing and certification of just about all constructing buildings, elements, systems and elements with the interesting exception of fireside resistant cables (exception in USA, Canada, Australia, Germany, Belgium and New Zealand where hearth resistant cable systems are required to be tested and accredited to the Standard Time Temperature protocol, similar to all different building constructions, components and components).
It is essential to understand that application requirements from BS, IEC, ASNZS, DIN, UL and so on. the place hearth resistive cables are specified for use, are solely ‘minimum’ requirements. We know right now that fires aren’t all the identical and research by Universities, Institutions and Authorities around the globe have recognized that Underground and some Industrial environments can exhibit very different fire profiles to those in above floor cellulosic buildings. Specifically in confined underground public areas like Road and Rail Tunnels, Underground Shopping facilities, Car Parks fireplace temperatures can exhibit a very fast rise time and may attain temperatures properly above those in above floor buildings and in far much less time. In USA at present electrical wiring techniques are required by NFPA 502 (Road Tunnels, Bridges and other Limited Access Highways) to face up to hearth temperatures as a lot as 1,350 Degrees C for 60 minutes and UK British Standard BS8519:2010 clearly identifies underground public areas similar to automobile parks as “Areas of Special Risk” where extra stringent check protocols for important electrical cable circuits may must be considered by designers.
Standard Time Temperature curves (Europe and America) plotted towards widespread BS and IEC cable checks.
Of course all underground environments whether or not street, rail and pedestrian tunnels, or underground public environments like purchasing precincts, car parks etc. could exhibit totally different fireplace profiles to those in above floor buildings as a result of In these environments the heat generated by any hearth can not escape as easily as it might in above ground buildings thus relying more on heat and smoke extraction gear.
For Metros Road and Rail Tunnels, Hospitals, Health care amenities, Underground public environments like buying precincts, Very High Rise, Theaters, Public Halls, Government buildings, Airports etc. this is notably important. Evacuation of these public environments is often sluggish even throughout emergencies, and it’s our accountability to make sure everyone is given the easiest probability of secure egress throughout hearth emergencies.
It can also be understood right now that copper Fire Resistant cables where put in in galvanized metal conduit can fail prematurely throughout hearth emergency because of a response between the copper conductors and zinc galvanizing inside the metal conduit. In เกจวัดแรงดันลมดิจิตอล United Laboratories (UL®) in America eliminated all certification for Fire Resistive cables the place installed in galvanized metal conduit for this reason:
UL® Quote: “A concern was brought to our consideration related to the efficiency of these products in the presence of zinc. We validated this discovering. As a results of this, we changed our Guide Information to indicate that each one conduit and conduit fittings that are out there in contact with fireplace resistive cables should have an interior coating freed from zinc”.
Time temperature profile of tunnel fires using vehicles, HGV trailers with totally different cargo and rail carriages. Graph extract: Haukur Ingason and Anders Lonnermark of the Swedish National Testing and Research Institute who introduced the paper on the First International Symposium in Prague 2004: Safe and Reliable Tunnels.
It would seem that some Standards authorities around the world might must evaluation the current test methodology at present adopted for fire resistive cable testing and perhaps align the performance of Life Safety and Fire Fighting wiring techniques with that of all the opposite hearth resistant constructions, components and methods so that Architects, building designers and engineers know that once they want a fire rating that the essential wiring system might be equally rated.
For many power, control, communication and knowledge circuits there’s one technology available which may meet and surpass all current fire checks and functions. It is a solution which is frequently utilized in demanding public buildings and has been employed reliably for over 80 years. MICC cable technology can present a total and complete answer to all the problems associated with the fireplace safety risks of recent versatile natural polymer cables.
The metallic jacket, magnesium oxide insulation and conductors of MICC cables make sure the cable is effectively fireplace proof. Bare MICC cables have no natural content material so merely can not propagate flame or generate any smoke. The zero fuel-load of those MICC cables ensures no heat is added to the fireplace and no oxygen is consumed. Being inorganic these MICC cables can’t generate any halogen or poisonous gasses in any respect together with Carbon Monoxide. MICC cable designs can meet all of the present and constructing fireplace resistance efficiency standards in all nations and are seeing a big increase in use globally.
Many engineers have previously thought-about MICC cable know-how to be “old school’ however with the new analysis in hearth performance MICC cable system are actually confirmed to have far superior fireplace performances than any of the newer extra fashionable versatile hearth resistant cables.
For additional info, go to www.temperature-house.com